Acrel AMC16Z-ZA Data Center Monitoring Device
3 Phase Energy Meter for Energy Monitoring of Data Center
Monitor A+B independent 2 channels of 3 phase incoming lines, Monitor 6 channels of passive switch input and 2 channels of switch output, Monitor residual current, 1 RS485(Modbus-RTU), Monitor 2-31st harmonic, Monitor temperature and humidity, 1 RS485(Modbus-RTU) , etc.
With the rapid development of data center, the energy consumption problem of data center is becoming more and more prominent. The energy management and power supply and distribution design of data center have become a hot issue. Efficient and reliable power distribution system scheme of data center is an effective way to improve the power consumption efficiency of data center and reduce the
energy consumption of equipment.
In order to realize energy saving in data center, it is necessary to monitor each electrical load first. However, there are many load circuits in data center. Traditional measuring instruments cannot meet the requirements of cost, volume, installation, construction and other aspects. In this case, the multi-circuit monitoring device which is suitable for centralized monitoring in data center is necessary to be used.
AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing’s electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring. All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.
Precision power distribution monitoring for data center
● Designed specifically for the power monitoring of data center
● A+B independent 2 channels of 3 phase incoming circuits
● Monitor U,I,P,Q,S,PF,EP,EQ,UN, neutral current, etc.
● Accuracy: 0.5
● Communication: 1 RS485(Modbus-RTU)(Optional)
● Monitor 6 channels of passive switch input, 2 channels of switch output
● Monitor 2-31st harmonic
● Monitor temperature and humidity
● Monitor residual current
Connect via CTs
Direct connect
number |
definition |
Explanation |
Remarks |
1 |
V+ |
Power Output |
Power supply 12V to AMC16Z-FA, AMC16Z-KA,AMC16Z-KD and touch screen,the power supply is forbidden to connect other devices (such as indicator light, buzzer) |
2 |
V- |
||
4 |
IA+ |
Current input phase A |
A-channel incoming three-phase current input |
5 |
IA- |
||
6 |
IB+ |
Current input phase B |
|
7 |
IB- |
||
8 |
IC+ |
Current input phase C |
|
9 |
IC- |
||
10 |
UN |
AC voltage neutral |
A-channel incoming three-phase voltage input |
11 |
UA |
AC voltage phase A |
|
12 |
UB |
AC voltage phase B |
|
13 |
UC |
AC voltage phase C |
|
PG |
Earth |
||
14 |
IA+ |
Current input phase A |
B-channel incoming three-phase current input |
15 |
IA- |
||
16 |
IB+ |
Current input phase B |
|
17 |
IB- |
||
18 |
IC+ |
Current input phase C |
|
19 |
IC- |
||
20 |
UN |
AC voltage neutral |
B-channel incoming three-phase voltage input |
21 |
UA |
AC voltage phase A |
|
22 |
UB |
AC voltage phase B |
|
23 |
UC |
AC voltage phase C |
|
PG |
Earth |
|
|
30 |
A |
RS485 communication |
Connect to touch screen or RS485 hub |
31 |
B |
||
50 |
DO1 |
Switch output |
Connect the buzzer |
51 |
|||
52 |
DO2 |
Connect indicator |
|
53 |
|||
61 |
Incoming line A |
Switch input |
OF+SD |
62 |
SD |
||
63 |
Lightning A |
c |
|
64 |
Incoming line B |
OF+SD |
|
65 |
SD |
||
66 |
Lightning B |
Judge the status of B-channel lightning protector |
|
69 |
Public end |
|
Switching common |
71 |
I1 |
Leakage |
Leakage 1st leakage current |
72 |
I2 |
Second leakage current |
|
79 |
COM |
Leakage common |
|
81 |
V- |
temperature and humidity |
Connect WH-3 temperature and humidity sensor |
82 |
DATE |
||
83 |
CLK |
||
84 |
V+ |
1.1 The measurement of the device is not accurate
*Check whether the wiring of voltage and current is correct, and whether the incoming and outgoing lines of current input are correct;
*Check whether the CT setting of the device corresponds to the actual CT used externally;
1.2 The voltage and current are measured correctly, but the power is not measured accurately.
*Check whether the current input direction is correct;
*Check whether the corresponding phase of each current loop is correct;The outgoing circuit shall be adjusted according to actual access.
1.3 Abnormal communication
*Check whether the communication cable is connected normally;
*Check whether the A and B terminals of communication are interlaced;
*Check whether the address of the device is set correctly and the communication baud rate is set correctly;
*When the communication of multiple devices is abnormal, first try whether the single communication is normal;
1.4 There is incoming voltage, current, and power, but electricity has no value.
*Check the CT ratio setting of the incoming line.
1.5 The current of AMC16Z-ZD has a value when the load has no current.
*Adjust the zero value of AMC16Z-ZD current.(the zero point of dc hall sensor is not consistent, the difference is large, need to be adjusted)
Other Question? Please contact us and we will get back to you as soon as possible.
Model |
Function description |
AMC16Z-ZA |
Monitor the full power parameters of A+B double-way three-phase AC incoming circuit, 6-way switch state monitoring, 2-way alarm output, 2-way leakage monitoring, 1-way temperature and humidity detection, 1-way RS485 communication, and phase-sequence detection. |
AMC16Z-FA |
Monitor the full power parameters of 24 branches of A+B double-way AC outgoing line, 1-way RS485 communication and phase adjustment. |
AMC16Z-FAK24 |
Monitor the full power parameters and switch state of 24 branches of A+B double-way AC outgoing line, 1-way RS485 communication and phase adjustment. |
AMC16Z-FAK48 |
Monitor the full power parameters and switch state of 48 branches of A+B double-way AC outgoing line, 1-way RS485 communication and phase adjustment. |
AMC16Z-KA |
Wet contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication. |
AMC16Z-KD |
Dry contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication. |
AMC16Z-AC220V |
AC220V extended power supply, and use when the monitoring circuit is beyond 96 branches of A+B |
IOT Platform
All electricity data can be transmitted to the IOT platform
Prepayment management
Electricity data analysis
Alarming
Issue report
ADL200/C Single Phase Meter
RS485(Modbus-RTU)
Multi-tariff
3 months historical energy data frozen storage
Measurement: Active kWh (positive and negative),
reactive power, U, I, P, Q, S, PF, F, etc.
ADW200 Series
Multi-channel Energy Meter
5A, 100A, 400A, 600A
Measure 4 channels of 3 phase circuits
ADL3000-E/C(DTSD1352-C) 3 Phase Meter
RS485(Modbus-RTU)
2 channels of RS485
Multi-tariff
1DI/1DO
3 channels of temperature measurement
2-31st harmonic
Frozen data on last 48 months, last 90 days
ADW210 Series
Multi-channel Energy Meter
Input current: 5A, 100A, 400A, 600A
Measure 4 channels of 3 phase circuits
AMC72 3 Phase Energy Meter
Input current: 5A, or 1A
RS485(Modbus-RTU)
2DI/2DO
THDi, THDu
SOE:event record
Measurement: Active kWh (positive and negative),
reactive power, U, I, P, Q, S, PF, F, etc.
ADF400L Series
Multi-channel Energy Meter
Measure 12 channels of 3 phase circuits,
or 36 channels of 36 single phase circuits
Input current: 3*1(6)A, 80A
APM830 Three Phase Energy Meter
Measurement: total electrical measurement,
Pulse output of energy
Demand data, Event log
Extreme value statistics
Power quality analysis
RS485(Modbus-RTU), 1 Profibus-DP
10DI+4DO, 8AI+4AO
Multi tariff, TF card storage
1 Ethernet, support Modbus-TCP, http, SMTP, DHCP protocol
Technical parameter |
AMC16Z-ZA |
||
Measured parameters |
Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power |
||
Zero ground voltage, neutral line current, total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF),telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity, environmental temperature and humidity. |
|||
Busbar voltage |
Rated |
220VAC |
|
Measurement |
±20% |
||
Overload |
Instant voltage 2times/second |
||
Current incoming circuit |
Rated |
Twice 5A |
|
Range |
0~6A |
||
Overload |
Duration 1.2 times, instantaneous 10 times/second |
||
Temp &humidity |
Temp range |
-40℃~+99℃ |
|
humidity range |
20%~90% |
||
Input frequency |
45~60Hz |
||
Measurement precision |
Inlet wire |
Voltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric energy level 1 |
|
Temp |
±1℃ |
||
Humidity |
±5% |
||
Auxiliary power supply |
Take electric signal(≤15W) |
||
Environment |
Temp |
Working:-15℃~55℃ Storage:-25℃~70℃ |
|
Humidity |
Relative humidity ≤93% |
||
Altitude |
≤2500m |
||
Switch output |
2-way 3A 250VAC/3A 30VDC |
||
Switch input |
6-way dry contact |
||
Communication |
RS485/Modbus-RTU |
||
Installation method |
DIN35mm Guide rail or bottom plate mounting |
||
IP grade |
IP20 |
||
Class of pollution |
2 |
||
Safety |
Insulation |
All terminals and the insulation resistance between the conductive pieces not less than 100MΩ |
|
Withstand voltage |
A-way voltage and current signal, B-way voltage and current signal, switch output and other ports should meet AC2kV 1min in pairs, the switch input and other ports should meet ac0.5kv 1mim, leakage current should be less than 2mA, no breakdown or flashover |
||
Electromagnet ic compatibility |
Anti static interference |
Level 4 |
|
Electrical fast transient pulse group |
Level 3 |
||
Anti-surge interference |
Level 4 |
||
Resistance to radiation of Radio frequency electromagnetic field |
Level 3 |
1. who are we?
We are a top manufacturer with over 1500 employees, over 300 R&D engineers in China, with CE, ROHS, IEC, EAC, MID, UL, FCC Certificates, etc.
Our Products: AC/DC electricity meters, current transformers, hall sensors, transducers, gateways, Motor protectors, wireless temperature monitoring, residual current relays, medical IT, IOT platform, other energy management systems, etc.
As a top-level provider of electrical solution service, we can help you save energy, reduce cost, improve energy efficiency and safety, realize intelligent, visual and fine management of energy, and provide data services for energy management.
2. What is your website?
www.acrel.sg
3. how can we guarantee quality?
Always a pre-production sample before mass production;
Always final Inspection before shipment;
4.what can you buy from us?
AC/DC Energy Meter, Hall Effect Sensor, Current Transformer, Current Transducer, Motor Protectors, Wireless Temperature Monitoring, Residual Current Relay, IOT Platform, etc.
5. why should you buy from us not from other suppliers?
147 computer software copyrights, 2 million meters, 1.5 million transformers, more than 100 design patents, 70 utility model patents.
6. what services can we provide?
Accepted Delivery Terms: FOB, CFR, CIF, EXW, DDU, Express Delivery, etc.
Accepted Payment Currency: USD, EUR, RMB, etc.
Accepted Payment Type: T/T, L/C, etc.
Language Spoken:English, Spanish, Chinese, etc.