BM200-DI series Single or Dual Input Current Isolated Safety Barrier
General
BM200 isolated safety barrier can transmit signals between the safe area and the dangerous area, and limit the energy transfer from the safe area to the dangerous area caused by the fault. The voltage, current, temperature, resistance signals generated by the equipment (transmitter) on the dangerous side are isolated and converted into corresponding linear voltage and current signals outputting to the safe area. The product requires independent power supply, and the input/output/power supply is isolated. It can be used in current source, two-wire, three-wire transmitter equipment.
Features
① DC voltage/current input
② Using magnetic isolation technology
③ Response time <400ms
④ TS35 rail installation
⑤ Plug-in terminal
⑥ Temperature drift coefficient: ≤200ppm/℃ at 0.5 level
Dimension
Structure
Application
BM200-DI/I-B11:
BM200-DI/I-C12:
BM200-DI/I-C22:
Type |
BM200-DI/I-B11、BM200-DI/I-C12、BM200-DI/I-C22 |
Channel type |
1 in 1 out, 1 in 2 out, 2 in 2 out |
Input type |
Current |
Output signal |
0~20mA/4~20mA (Distribution voltage: 14.0V/20mA) |
Output Signal |
0~20mA /4~20mA (safety side output); Load resistance: ≤550Ω |
Transmission accuracy |
0.2% |
Temperature drift |
50ppm |
Response time |
5ms to reach 90% of final value |
Supply voltage |
20~35V DC |
Consumption |
24V power supply, 20mA output: ≤70mA (one in, one out) ≤110mA (one in, two out) ≤160mA (two in and two out) |
Working temperature |
-20℃~+60℃ |
Storage temperature |
-40℃~+80℃ |
Relative humidity |
≤95%RH, no condensation, no corrosive gas place |
Altitude |
≤2500m |
Protection level |
IP20 |
Weight |
About 110g (12.5mm shell) About 150g (22.5mm shell) |
Installation |
Din-rail mounted |
Dielectric strength |